XN-ACPWR-150W | XN-ACPWR-600W | XN-ACPWR-920W | XN-ACPWR-1200W* | XN-ACPWR-2000W** | |
---|---|---|---|---|---|
Voltage Input Range (Nominal) |
100-127/200-240 VAC |
100-127/200-240 VAC |
100-127/200-240 VAC |
100-127/200-240 VAC |
100-127/200-240 VAC |
Line Frequency Range | 47Hz to 63Hz | 47Hz to 63Hz | 47Hz to 63Hz | 47Hz to 63Hz | 47Hz to 63Hz |
Power Supply Input Socket | IEC/EN60320 C14 | IEC/EN60320 C14 | IEC/EN60320 C14 | IEC/EN60320 C16 | IEC/EN60320 C16 |
Power Cord Input Plug | IEC/EN60320 C13 | IEC/EN60320 C13 | IEC/EN60320 C13 | IEC/EN60320 C15 | IEC/EN60320 C15 |
Operating Temperature |
0°C to 50°C (32°F to 122°F) Normal Operation |
0°C to 50°C (32°F to 122°F) Normal Operation |
0°C to 50°C (32°F to 122°F) Normal Operation |
0°C to 50°C (32°F to 122°F) Normal Operation |
0°C to 45°C (32°F to 113°F)*** |
* 200-240VAC is required to achieve full 1200W output. If run at 100-120 VAC, output is limited to 860W
** 200-240 VAC is required to achieve full 2000W output. If run at 100-120 VAC, output is limited to 1100W
*** At sea-level, 0°C to 40°C (32°F to 104°F) at1500 m; 0°C to 35°C (32°F to 95°F) at3000 m
Model | Internal Fixed Power Supply Unit (PSU)* | Secondary Power Supply Unit (PSU)** |
---|---|---|
5420F-24T-4XE | 120WAC PSU | XN-ACPWR-150W |
5420F-24P-4XE | 660WAC PSU | XN-ACPWR-600W |
5420F-24S-4XE | 150WAC PSU | XN-ACPWR-150W |
5420F-48T-4XE | 120WAC PSU | XN-ACPWR-150W |
5420F-48P-4XE | 860WAC PSU | XN-ACPWR-920W |
5420F-48P-4XL | 860WAC PSU | XN-ACPWR-920W |
5420F-8W-16P-4XE | 660WAC PSU | XN-ACPWR-600W |
5420F-16W-32P-4XE | 1200WAC PSU | XN-ACPWR-1200W |
5420F-16MW-32P-4XE | 1200WAC PSU | XN-ACPWR-1200W |
* Internal Fixed PSU is non-orderable and comes pre-installed with each 5420F model.
** Secondary PSU provides power redundancy in 5420F non-PoE models and enables maximum PoE Power Budget in 5420F PoE models (see table below). Model/PSU combinations other than those listed above are blocked physically or in software.
Model | PoE Budget with Single Internal Fixed PSU | PoE Budget with Recommended Secondary PSU |
---|---|---|
5420F-24P-4XE | 380W | 720W |
5420F-48P-4XE | 740W | 1480W |
5420F-48P-4XL | 740W | 1480W |
5420F-8W-16P-4XE | 480W | 960W |
5420F-16W-32P-4XE | 872W*/960W** | 1437W*/1874W** |
5420F-16MW-32P-4XE | 860W*/960W** | 1425W*/1862W** |
* @100-120 VAC
** @ 200-240 VAC
Model | Primary Power Supply Unit (PSU)* | Secondary Power Supply Unit (PSU)* |
---|---|---|
5420M-24T-4YE | XN-ACPWR-150W | XN-ACPWR-150W |
5420M-24W-4YE | XN-ACPWR-920W | XN-ACPWR-920W |
5420M-48T-4YE | XN-ACPWR-150W | XN-ACPWR-150W |
5420M-48W-4YE | XN-ACPWR-920W or XN-ACPWR-2000W | XN-ACPWR-920W or XN-ACPWR-2000W |
5420M-16MW-32P-4YE | XN-ACPWR-920W or XN-ACPWR-2000W | XN-ACPWR-920W or XN-ACPWR-2000W |
* Primary PSU is required; Secondary PSU provides power redundancy and enables maximum PoE Budget in 5420M PoE models (see table below). Model/PSU combinations other than those listed above are blocked physically or in software.
Model |
1 x 920W |
2 x 920W |
1 x 2000W @ 100-120 VAC |
1 x 2000W @ 200-240 VAC |
1x 920W & 1 x 2000W @ 100-120 VAC |
1x 920W & 1 x 2000W @ 200-240 VAC |
2 x 2000W @ 100-120 VAC |
2 x 2000W @ 200-240 VAC |
---|---|---|---|---|---|---|---|---|
5420M-24W-4YE | 720W | 1440W | — | — | — | — | — | — |
5420M-48W-4YE | 804W | 1558W | 884W | 1440W | 1212W | 2076W | 1704W | 2880W |
5420M-16MW-32P-4YE | 787W | 1541W | 867W | 1440W | 1195W | 2059W | 1687W | 2400W |
Switch Model | Minimum Power Consumption (W) | Minimum Heat Dissipation (BTU/hr) | Maximum Power Consumption (W)* | MaximumHeat Dissipation (BTU/hr)** |
---|---|---|---|---|
5420F Switches | ||||
5420F-24T-4XE | 24 | 81 | 62 | 211 |
5420F-24P-4XE | 37 | 127 | 833 | 387 |
5420F-24S-4XE | 35 | 119 | 114 | 388 |
5420F-48T-4XE | 31 | 106 | 75 | 255 |
5420F-48P-4XE | 48 | 164 | 1674 | 663 |
5420F-48P-4XL | 49 | 168 | 1657 | 604 |
5420F-8W-16P-4XE | 37 | 127 | 1092 | 452 |
5420F-16W-32P-4XE | 46 | 156 | 2150 | 785 |
5420F-16MW-32P-4XE | 50 | 172 | 2152 | 790 |
* Includes maximum PoE load (W) through the switch
**Does not include PoE load heat dissipated through external electronic load
Switch Model | Minimum Power Consumption (W) | Minimum Heat Dissipation (BTU/hr) | Maximum Power Consumption (W)* | MaximumHeat Dissipation (BTU/hr)** |
---|---|---|---|---|
5420M-24T-4YE | 28 | 95 | 57 | 194 |
5420M-24W-4YE | 43 | 148 | 1601 | 551 |
5420M-48T-4YE | 34 | 117 | 68 | 232 |
5420M-48W-4YE | 72 | 245 | 3090 | 716 |
5420M-16MW-32P-4YE | 69 | 234 | 2564 | 560 |
* Includes maximum PoE load (W) through the switch
**Does not include PoE load heat dissipated through external electronic load