Warning
Be sure to connect the chassis ground wire before you connect
any power cables.
Warning
Be sure to disconnect the ground wire after you disconnect all
power cables.
To connect the ground wire:
-
Verify that the DC circuit is de-energized.
-
Identify the grounding point on the front panel of
the power supply.
1 = Grounding point |
2 = Ground wire |
-
Insert an M3.5 screw (provided) through the ring
terminal and into the grounding point on the power supply.
-
Tighten the screw to 12.6 in‑lb (1.42
N m).
-
Connect the other end of the wire to a known
reliable earth ground point at your site.