Connecting an 1100 W DC Power Supply to the Source Voltage

Summit 1100 W DC power supply units must connect to a –48V source.

The DC power connection at your facility must be made by a qualified electrician, following these instructions.

Warning

Warning

Always make sure that the DC circuit is de-energized before connecting or disconnecting the DC power cables on the DC power supply.
Caution

Caution

Provide proper connection and strain relief on the DC power cables in accordance with all local and national electrical codes.
  1. Verify that the DC circuit is de-energized.
  2. Attach an ESD-preventive wrist strap to your bare wrist and connect the metal end to an appropriate ground point on the rack.
  3. Verify that the ground wire is attached to the power supply.
  4. Insert a screwdriver into both slots on the top of the terminal connector and loosen the screws enough to accommodate a stripped power input cable.
  5. Insert the DC power cables into the connector.
    1. Slide the end of the positive wire (–48 V RTN) into the positive terminal (labeled +, on the left side of the connector).
    2. Tighten the screw on the top of the positive terminal connector to between 4.4 in‑lb (0.50 N m) and 7.1 in‑lb (0.8 N m).
      See Inserting the DC Power Cables into the Connector.
      Click to expand in new window
      Inserting the DC Power Cables into the Connector
    3. Slide the end of the negative wire (–48 V) into the negative terminal (labeled , on the right side of the connector).
    4. Tighten the screw on the top of the negative terminal connector to between 4.4 in‑lb (0.50 N m) and 7.1 in‑lb (0.8 N m).
  6. Insert the connector into the slot on the power supply.
    See Inserting the Connector into the Power Supply.
    Click to expand in new window
    Inserting the Connector into the Power Supply
  7. Connect the cables to the DC source voltage, using hardware appropriate to the installation site and following local and national electrical codes.
  8. Energize the DC circuit.

Leave the ESD strap permanently connected to the rack, so that the strap is always available when you need to handle ESD-sensitive components.

Connect network interface cables to the switch, using the instructions in Connect Network Interface Cables.