Connecting DC Power Cables to a 550 W DC Power Supply
The DC power connection at your facility must be made by a qualified electrician.

Warning
Always make sure that the
DC circuit is de-energized before connecting or disconnecting the DC power cables on
the
550 W DC power supply.

Caution
Provide proper connection and strain relief
on the DC power cables in accordance with all local and national electrical
codes.
To connect the DC power cables to the 550 W DC power supply, follow these steps:
- Verify that the DC circuit
is de-energized.
- Attach an
ESD-preventive wrist strap to your bare wrist and connect the metal end to an
appropriate ground point on the rack.
-
Verify that the ground wire is attached to the
power supply.
-
Connect the DC power input cables as follows:
-
On each terminal, loosen the screw enough
to allow the spade terminal to slide underneath the captive square
washer (see Connecting the DC Power Cables: Part 1).
-
Slide the spade terminal of the negative wire
(–48 V) under the captive square washer on the negative terminal
(labeled –).
-
Slide the spade terminal of the positive wire
(–48 V RTN) under the captive square washer on the positive terminal
(labeled +).
Connecting the DC Power Cables: Part 1
-
Tighten both screws on the
terminal block to 7 in‑lb (0.79 N m), as shown in Connecting the DC Power Cables: Part 2.
Connecting the DC Power Cables: Part 2
-
Snap the cover into place over the terminal
block.
- Energize the DC circuit.