Connecting the Ground Wire to a 550 W DC Power Supply
You need a #1 Phillips screwdriver to secure the ground wire to
the power supply.
Warning
Be sure to connect the chassis ground wire before you connect any power cables.
Warning
Be sure to disconnect the ground wire after you disconnect all power
cables.
To connect the ground wire to a Summit 550 W DC power supply, follow these steps:
- Verify that the DC circuit
is de-energized.
- Attach an
ESD-preventive wrist strap to your bare wrist and connect the metal end to an
appropriate ground point on the rack.
- Slide the cover off the
terminal block.
-
Identify the grounding point at the left of the
terminal block.
-
Connect the ground wire to the grounding point as
follows:
-
Loosen the screw enough to allow the spade
terminal to slide underneath the captive square washer.
Connecting the Ground Wire
-
Slide the spade terminal of the ground
wire under the captive square washer.
-
Tighten the screw to 7
in‑lb (0.79 N m) as shown in Securing the Ground Wire.
- Connect the other end
of the wire to a known reliable earth ground point at your site.
-
Connect the power supply to the source, following the instructions in Connecting a 550 W DC Power Supply to the Source Voltage.