Connecting a 300 W DC Power Supply to the Source Voltage
Two 300 W DC power supplies are available: model 10933
(front-to-back airflow) and model 10944 (back-to-front airflow). Both can connect to
either a +24 V or a –48 V power source.
The connection instructions, starting at step 4,
are different depending upon whether you are connecting to a +24 V power source or a
–48 V power source.
The DC power connection at your facility must be made by a
qualified electrician, following these instructions.

Warning
Always make sure that the DC circuit is de-energized before connecting or disconnecting
the DC power cables on the DC power supply.

Caution
Provide proper
connection and strain relief on the DC power cables in accordance with all local and
national electrical codes.
- Verify that the DC circuit
is de-energized.
- Attach an
ESD-preventive wrist strap to your bare wrist and connect the metal end to an
appropriate ground point on the rack.
- Slide the cover off the
terminal block.
-
Connect the DC power
input cables as follows:
When connecting the power
supply to a +24 V source:
-
On each terminal, loosen the screw
enough to allow the spade terminal to slide underneath the captive square washer.
Loosening
Terminal Screws (Connecting to a +24 V Source)
-
Slide the spade terminal
of the negative
wire (–24 V) under the captive square washer on the negative terminal
(labeled –24 V).
-
Slide the spade terminal
of the positive
wire (+24 V) under the captive square washer on the positive terminal
(+24 V).
-
Tighten both screws on
the terminal block to 11 in‑lb (1.25 N m).
Tightening
Terminal Screws (Connecting to a +24 V Source)
When connecting the power
supply to a –48 V source:
-
On each terminal, loosen the screw
enough to allow the spade terminal to slide underneath the captive square washer.
Loosening
Terminal Screws (Connecting to a –48 V Source)
-
Slide the spade terminal
of the negative
wire (–48 V) under the captive square washer on the negative terminal
(labeled –48 V).
-
Slide the spade terminal
of the positive
wire (–48 V RTN) under the captive square washer on the positive terminal
(labeled RTN).
-
Tighten both screws on
the terminal block to 11 in‑lb (1.25 N m).
Tightening
Terminal Screws (Connecting to a –48 V Source)
- Slide the cover into place
over the terminal block.
- Connect the cables to the
DC source voltage, using hardware appropriate to the installation site and following
local and national electrical codes.
- Energize the DC circuit.
Leave the ESD strap permanently connected to the
rack, so that the strap is always available when you need to handle ESD-sensitive
components.
You can now connect network interface cables to the switch, using
the instructions in Connecting Network Interface Cables.