Connecting the Ground Wire to a 300 W DC Power Supply
Follow these steps to connect the ground wire to a
Summit 300 W DC power supply.
Warning
Be sure to connect the chassis ground wire before you connect any power cables.
Warning
Be sure to disconnect the ground wire after you disconnect all power
cables.
- Verify that the DC circuit
is de-energized.
- Attach an
ESD-preventive wrist strap to your bare wrist and connect the metal end to an
appropriate ground point on the rack.
- Pull the cover off the terminal
block.
-
Identify the grounding point on the front panel of
the power supply.
-
Connect the ground wire to the grounding point as
follows:
-
Insert a 6-32 UNC screw (provided) through
the ring terminal and into the grounding point on the power
supply.
-
Tighten the screw to 12.6 in‑lb
(1.42 N m).
- Connect the other end
of the wire to a known reliable earth ground point at your site.
-
Connect the power supply to the source, following the instructions in Connecting a 300 W DC Power Supply to the Source Voltage.