Connect DC Power Cables to an 750 W DC
Power Supply
The DC power connection at your facility must be made by a qualified electrician.
Warning
Always make sure that the DC circuit is de-energized before connecting or
disconnecting the DC power cables on the 750 W DC power supply.
Caution
Provide proper
connection and strain relief on the DC power cables in accordance with all local and
national electrical codes.
To connect the DC power cables to the 750 W DC power supply, follow these steps:
- Verify that the DC circuit
is de-energized.
- Attach an
ESD-preventive wrist strap to your bare wrist and connect the metal end to an
appropriate ground point on the rack.
-
Verify that the ground wire is
attached to the power supply.
-
Insert a screwdriver into both
slots on the top of the terminal connector and loosen the screws enough to
accommodate a stripped power input cable.
-
Insert the DC power cables into
the connector.
-
Slide the end of the positive wire
(–48 V RTN) into the positive terminal (labeled +, on the left
side of the connector).
-
Tighten the screw on the
top of the positive terminal connector to between 4.4 in‑lb (0.50 N m)
and 7.1 in‑lb (0.8 N m).
Inserting the
DC Power Cables into the Connector
-
Slide the end of the negative wire
(–48 V) into the negative terminal (labeled –, on the right
side of the connector).
-
Tighten the screw on the
top of the negative terminal connector to between 4.4 in‑lb (0.50 N m)
and 7.1 in‑lb (0.8 N m).
-
Insert the connector into the
slot on the power supply.
Inserting the
Connector into the Power Supply
- Connect the cables to the
DC source voltage, using hardware appropriate to the installation site and following
local and national electrical codes.
- Energize the DC circuit.