Installing a Summit 750 W AC Power Supply into the EPS-C2
The EPS-C2 chassis is shipped with slots 2 and 3 covered and slot 1 open.
We recommend that you install a power supply first in slot 1, but
this is not required. You can install power supplies into any of the slots in the
EPS-C2 chassis. The installation sequence does not affect the performance of the
power supply units, but empty slots must be covered at all times.
Warning
To prevent an
electrical hazard, make sure that the AC power cord is not connected to the
power supply before you install the power supply in the power supply bay.
After the EPS-C2 has been installed in a rack, do the following to
install a 750 W AC power supply in an EPS-C2 chassis:
-
If necessary, grasp the two tabs on either side of
the slot cover and pull gently to remove it from the front of the EPS-C2
chassis.
Removing a
Blank Panel from the EPS-C2 Chassis
-
Verify that the power supply is right side up (there
is a sticker labeled “This Side Up”).
-
Carefully slide the power supply all the way into
the slot in the EPS-C2 chassis (see Installing a 750 W AC Power Supply in an EPS-C2 Chassis).
-
Push the power supply in until the latch snaps into place.
Caution
Do not slam the power supply into the
chassis.
Installing a 750 W AC Power Supply in an
EPS-C2 Chassis
Note
If power supplies are not installed in
all three slots, be sure to install a cover over each unoccupied slot.
Unoccupied slots must always be covered to maintain proper system
ventilation and EMI levels.
Repeat the procedure to install each
additional power supply.